lunar bridge ul 1741 ul 67
Certificate of Compliance
Certificate: 80121278
Master Contract: 302773
Project: 80250326
Date Issued: 2025-04-21
Issued to:
Issued by:
Lunar Energy, Inc
755 Ravendale Drive
Mountain View, California
94043
United States
Peter Lim
Peter Lim
Attention: Taylor Mckenzie
The products listed below are eligible to bear the CSA Mark shown with adjacent
indicator 'US'
!
PRODUCTS
Class 5311 89 POWER SUPPLIES - Distributed Generation Power Systems Equipment - Certified to U.S. Standards
Microgrid Interconnect Device ‑ Panelboard
| Model(s) |
|---|
| 90-06801A(a.k.a Lunar Bridge) |
Electrical Ratings:
- Maximum AC Current: 200A
- Grid Frequency: 60 Hz
- Nominal Voltage (ac): 120/240 V Split-phase
- Maximum Main AC Overcurrent Protection rating: 200A
- Maximum Solar Breaker rating: 50A
QD-1397 Rev 2019-04-30
Certificate: 80121278
Master Contract: 302773
Project: 80250326
Date Issued: 2025-04-21
- Branch circuit bus rating (per stub rating): 200A
- Maximum Number of branch circuits: 40
- Enclosure Ratings Metal Enclosure: Type 3R
- Ambient Operating Temp: -40°C to +60°C (-40°F to +140°F)
- OVC IV, Pollution Degree 3
- Maximum Short-Circuit Current Rating (SCCR): 22KA
- Maximum Sum of the Short Circuit Current rating (SCCR): 22KA Main breaker Assembly
Conditions of Acceptability:
- Total branch output current shall not exceed 200A (ac) Max.
- Bare buses and connections are bare, connection shall meet either the minimum spacings specified in Table 26.1 as per UL1741 spacing requirement or Table 16.1 of UL67 or CSA C22.2 No.29 Table 2 whichever is the highest.
- All openings must meet the manufacturer’s recommended fitting to meet the enclosure rating.
- All listed insulation barriers and shields must be certified to minimum flame rating of V2 as per CSA 0.17(R2018) and/or UL94 unless otherwise stated in the critical component.
- This evaluation does not include metering measurements, it is treated as an intent for internal system application only.
- It is intended for use with Lunar Model: 10-005025 (a.k.a Lunar Inverter), and other Lunar associated safety approved devices only.
- Where applicable for metering device, associated Electromagnetic Immunity tests are to be conducted at end system level.
- When the Bridge is not used as a main panel (when the Bridge is not installed at the service entrance), the Neutral-to-Ground bonding wire MUST NOT be installed in the Bridge enclosure. Ensure that Neutral and Ground are properly bonded in the upstream equipment at the service entrance.
- When the Bridge is to be used as the main panel, installation shall have Neutral-to-Ground bonding wire in the Bridge.
- Conformal coating process as per document numbers 10-003104 and 10-003105 (See Att5 PCB Layouts).
- If installed in environments with temperatures below 0°C, the circuit breaker in the panelboard should not be considered reliable for overload protection. Separate overload protection, as mandated by both CEC and NEC, must be implemented in such conditions.
- The product’s Power Line Communication (PLC) functionality and usage were not assessed as part of this evaluation. Should such functionality be required for the intended end-use application, a separate and dedicated evaluation shall be conducted.
- Please refer to the verification of Conformity Letter 80233547 VOC for additional information on the Power Control System (PCS).
- Construction of panel with service entrance rating:
a. Main breaker shall be installed with accepted UL and/or CSA listed breaker, Square D QOM2200VH or smaller rating.
b. Line side barrier shall be installed in line side terminal: UL recognized.
c. Neutral is bonded to grounded by bonding jumper.
d. The “service disconnection”: label shall apply close to main breaker.
APPLICABLE REQUIREMENTS
UL 1741:2021 - Third Edition - Including revisions through October 23, 2024 - UL Standard for Safety Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources
UL 3141 (Issue 1) - SUBJECT - UL Outline for Investigation for Power Control Systems
Certificate: 80121278
Master Contract: 302773
Project: 80250326
Date Issued: 2025-04-21
Notes:
Products certified under Class(es) C531189 have been certified under CSA’s ISO/IEC 17065 accreditation with the Standards Council of Canada (SCC). www.scc.ca
!
!
Supplement to Certificate of Compliance
Certificate: 80121278
Master Contract: 302773
The products listed, including the latest revision described below,
are eligible to be marked in accordance with the referenced Certificate.
!
Product Certification History
| Project | Date | Description |
|---|---|---|
| 80250326 | 2025-04-21 | Update Report 80121278(80219669) to include PCS measurement functionality and increase main breaker rating to 200A(Reference to further update on the Project 80122022 for Panel control)和 based on completed project 80233547 for PCS.Also update model number from90-001221to new model number:90-06801A. |
| 80219669 | 2024-09-25 | Update report 80121278 to include alternate Construction.(See attached Lunar Bridge Type B Impact analysis for details) |
| 80121278 | 2024-05-04 | To perform Model Certification to ESS Grid Interconnect Device used in Lunar Energy Rechargeable Lithium-Ion Battery Stationary Home Energy Storage Product. |