san jose master file lfp

| SCOPE OF WORK

GENERAL NOTES TABLE OF CONTENTS
SCOPE OF WORK
GENERAL NOTES PAGE # DESCRIPTION
SYSTEM SIZE:6.66KW DC,9.60KW AC
MODULES:(18)LG LG370N1K-A6
INVERTER(S):(1)LUNAR ENERGY 9.6KW[240V][W/L2-ESS-20KWH BATTERY]
OPTIMIZER UNIT(S):(18)LUNAR MAXIMIZER
RACKING:TAMARACK2.3
ATTACHMENT:TAMARACKL-FOOT
ENERGY STORAGE SYSTEM:
(1)LUNAR ENERGY L2-ESS-20KWH BATTERY
MICROGRID INTERCONNECT DEVICE(MID)OPTIONS: THIS PROJECT SHALL COMPLY WITH LOCAL ORDINANCES
PROPER ACCESS AND WORKING CLEARANCE WILL BE PROVIDED
ALL ELECTRICAL WORK SHOWN ON THESE PLANS WILL BE COMPLETED BY THE UNDERSIGNED
ALL APPLICABLE PV EQUIPMENT LISTED AND COMPLIANT WITH UL2703,UL1741,UL3141,AND UL61730
ALL APPLICABLE ESS EQUIPMENT LISTED AND COMPLIANT WITH UL9540
ALL ROOF PENETRATIONS TO BE SEALED WITH A HIGH PERFORMANCE ROOF SEALANT SUCH AS CHEMLINK M1 ADHESIVE
THE SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND THE UTILITY IS OBTAINED
IF THE EXISTING MAIN BANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE IT IS NECESSARY TO PV1.0
PV2.0
PV2.1
PV3.0-3.1
PV4.0-4.3
PV6.0-6.4 COVER SHEET
SITE PLAN
EQUIPMENT LAYOUT
STRUCTURE DETAIL LAYOUT
ELECTRICAL
BATTERY MOUNTING DETAILS
(1) LUNAR ENERGY L2-ESS-20KWH BATTERY
MICROGRID INTERCONNECT DEVICE(MID)OPTIONS:
OPTION A:(1)LUNAR BRIDGE(MID)
OPTION B:(1)CONNECTDER METER SOCKET ADAPTER(MID)
W/ LUNAR METER ADAPTER CONTROLLER UTILITY IS OBTAINED
·IF THE EXISTING MAIN PANEL DOES NOT HAVE VERIFIABLE GROUNDING ELECTRODE,IT IS NECESSARY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE
·EACH MODULE WILL BE GROUNDED AS PER UL2703 AND/or UL61730 APPROVED METHOD USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE MODULE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
·A LADDER SHALL BE IN PLACE FOR THE INSPECTION IN COMPLIANCE WITH CAL-OSHA REGULATIONS
·ALL WORK SHALL COMPLY WITH 2025 CEC,2025 CRC,2025 CBC MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION INSTRUCTIONS.
·PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2025 CEC.
·PHOTOVOLTAIC SYSTEM INVERTER IS UNGROUNDED,NO CONDUCTORS ARE SOLIDLY GROUNDED IN THE INVERTER
·MODULES CONFORM TO AND ARE LISTED UNDER UL61730.
·INVERTER CONFORMS TO AND IS LISTED UNDER UL1741.
·ELECTRICAL EQUIPMENT AND MATERIAL TO BE LISTED,LABELED,AND INSTALLED PER THE CEC,THE
WIND EXPOSURE:C
WIND SPEED:120mph
GROUND SNOW LOAD:0psf
OCCUPANCY:PRIMARY RESIDENCE
CONSTRUCTION TYPE:RESIDENTIAL
FIRE SPRINKLER:NONE
CEC 2025,CBC 2025,2025 CFC,2025 CRC
MASTER FILE FOR LUNAR ENERGY 9.6KW [240V] PV INVERTER & 20KWH BATTERY UNIT
This approval is for compliance to the current adopted building codes for the proposed Solar System only. It is the owner's/applicant's responsibility to ensure that the proposed installation of solar systems and associated equipment is on legally permitted structures. If determined by inspection staff the proposed solar system is installed on non-permitted structures, any required modifications needed for code compliance will be at the owner's/applicant's expense
NOTES FOR INSPECTORS:
1) BATTERY CAN BE INSTALLED INDOORS OR OUTDOORS
2) AVOID INSTALLING IN LOCATIONS WITH FLAMMABLES, HEATING EQUIPMENT, OR
1) BATTERY CAN BE INSTALLED INDOORS OR OUTDOORS
2) AVOID INSTALLING IN LOCATIONS WITH FLAMMABLES, HEATING EQUIPMENT, OR WATER NEARBY PER MII'S
3) MUST NOT BE INSTALLED IN HABITABLE SPACE R328.4
4) MUST BE LOCATED OUT OF THE WAY OF VEHICLE PATH OR PROTECTED BY BOLLARDS R328.8
5) FOLLOW MANUFACTURER'S INSTALLATION INSTRUCTIONS (MII'S) FOR INSTALLATION
Reviewed for Code Compliance
City of San Jose, Building Division
Building Electrical
Plumbing Mechanical
Kiet Pham (408) 535-7773
No. 24102993 Date: 07/02/2026
COVER SHEET
PV 1.0

MORE THAN TWO FEET INTO ANY SETBACK AREA. AND POWER INVERTERS MAY PROJECT HORIZONTALLY FOR A DISTANCE OF NOT NOTE: THE BATTERY SHALL COMPLY WITH 20.30.400.d. TANKLESS WATER HEATERS INVERTER W/ 20kWh INTEGRATED ESS SYSTEM (N) LUNAR ENERGY 9.6KW [240V] [240V, 11.5kW] ROOF AREA OCCUPIED BY SOLAR: 15.94% · TOTAL ROOF AREA: 2202.81 SQFT · TOTAL PV AREA: 351.00 SQFT · HORIZONTAL RIDGE. CFC 605.11.2.2 (IRC R324.6.2) MINIMUM 18" SETBACK IS REQUIRED ON BOTH SIDES OF LESS OF THE PLAN VIEW TOTAL ROOF AREA, A FOR PHOTOVOLTAIC ARRAYS OCCUPYING 33% OR · (N) MICROGRID INTERCONNECT DEVICE (OPTION A) 1" = 5.33333'

THE PROPOSED ENERGY STORAGE SYSTEM WILL NOT BE INSTALLED IN HABITABLE SPACE AND BE AWAY FROM FLAMMABLE OR EXPLOSIVES.

THE PROPOSED ENERGY STORAGE SYSTEM MAY PROJECT HORIZONTALLY FOR A DISTANCE OF NOT MORE THAN TWO FEET INTO ANY SETBACK AREA.

FOR OUTDOOR APPLICATION THE ENERGY STORAGE SYSTEM WILL PLACED IN A SHADED AREA, NOT IN SUNLIGHT.

LEGEND

LEGEND M METER W/ METER COLLAR ADAPTER MP MAIN SERVICE PANEL BLP BACKUP LOAD PANEL JB JUNCTION BOX IWB INVERTER W/ BATTERY MID MICRO-GRID INTERCONNECTION DEVICE RSD RAPID SHUTDOWN SWITCH

CONTRACTOR INSTALLED

LUNAR ENERGY 755 RAVENDALE DR, MOUNTAIN VIEW, CA 94043 Phone: (650) 351-2060 Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance City of San Jose, Building Division Building Electrical Plumbing Mechanical Kiet Pham (408) 535-7773 No. 24-102993 Date: 07/02/2026

SITE PLAN

PV2.0



#MODULES PER ARRAY ROOF TYPE ATTACHMENT ROOF HEIGHT FRAME MATERIAL FRAME TYPE FRAME SIZE OC SPACING
AR-01 6 COMP SHINGLE TAMARACK L-FOOT ONE STORY WOOD WOOD RAFTER WITH COLLAR TIE 2"x6" 24"O.C.
AR-02 12 COMP SHINGLE TAMARACK L-FOOT ONE STORY WOOD WOOD RAFTER WITH COLLAR TIE 2"x6" 24"O.C.

LUNAR MAXIMIZER (12) OPTIMIZER UNITS 3'-2

DESIGN CRITERIA

MODULES: 18 MAX DISTRIBUTED LOAD: 3 PSF SNOW LOAD: 0 PSF WIND SPEED: 120 MPH 3-SEC GUST. LAG SCREWS: 5/16"x 2.5" MIN EMBEDMENT NOTE: INSTALLERS TO VERIFY RAFTER SIZE, SPACING AND SLOPED SPANS, AND NOTIFY E.O.R. OF ANY DISCREPANCIES BEFORE PROCEEDING.

WEIGHT PER SQ FT 833.5 / 351.00 sq.ft.= WEIGHT PER MOUNT 833.5 / 29 = 28.7 MODULE DIMENSION (LxW) 68.5" x 41.0"= 19.50 sq.ft

ITEM #OR LIN FT WEIGHT PER (lbs) TOTAL WEIGHT (lbs)
MODULES 18 41.00 738.00
RAILS 109.69 0.4 47.8
ATTACHMENTS 29 0.65 18.85
TILT LEGS 0 3.5 0
OPTIMIZER UNITS 18 1.6 28.8
TOTAL WEIGHT 833.5 lbs
MODULE DIMENSION (LxW) 68.5" x 41.0"= 19.50 sq.ft
WEIGHT PER MOUNT 833.5 / 29 = 28.7 Ibs/Mount
WEIGHT PER SQ FT 833.5 / 351.00 sq.ft. = 2.4 Ibs/sq.ft.

CONTRACTOR INSTALLED

LUNAR ENERGY 755 RAVENDALE DR, MOUNTAIN VIEW, CA 94043 Phone: (650) 351-2060 Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A DATE:11 June 2026

STAMP SPACE

DETAIL LAYOUT

PV3.0


CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance

City of San Jose, Building Division Building Electrical Plumbing Mechanical Kiet Pham (408) 535-7773

No. 24-102993 Date: 07/02/2026

MOUNTING LAYOUT

PV3.1


STRING B, ARRAY 2 (1) STRING OF (9) MODULES (9) LUNAR MAXIMIZER OPTIMIZER UNITS (9) LG LG370N1K-A6 (370W) MODULES SYSTEM SIZE: 6660W DC, 9600W AC & ESS 20 kWh

LISTED FOR 75 DEGREES. ALL CONDUCTORS AND TERMINATIONS SHALL BE CU PER 250.66 (A) AT THE MAIN PANEL, GEC WILL BE SIZED AS #6 AWG EXCEPTION: WHEN ESTABLISHING NEW GROUND ROD/UFER PER 250.52 SIZE GEC FROM PANEL GROUND BAR TO SIZE EGC PER 250.122 GROUNDING NOTES:

LUNAR BATTERY PACK 20KWH (STACK OF4 BATTERY MODULES WITH 9.6KW INVERTER)

(2) 8 AWG THHN/THWN-2 (4) 10 AWG THHN/THWN-2 (2) 10 AWG PV WIRE CONDUCTOR (RED/BLACK)

NEUTRAL (WHITE) *ALL WIRE ASSUMED TO BE CU UNLESS OTHERWISE SPECIFIED

THHN/THWN-2 (1) 10 AWG THHN/THWN-2 (1) 10 AWG 100A MAIN BREAKER 100A BUSBAR LOADS PANEL BACKED UP NEW 100A

CONDUIT SCHEDULE*ALL WIRE ASSUMED TO BE CU UNLESS OTHERWISE SPECIFIED
GROUND
# CONDUIT CONDUCTOR(RED/BLACK) NEUTRAL(WHITE) (GREEN) (BARE COPPER)
1 NONE (2)10AWG PVWIRE NONE NONE (1)6AWG
2 3/4"EMT (4)10AWGTHHN/THWN-2 NONE (1)10AWGTHHN/THWN-2 NONE
3 3/4"EMT (2)8AWGTHHN/THWN-2 (1)8AWGTHHN/THWN-2 (1)10AWGTHHN/THWN-2 NONE
4 1"EMT (2)3AWGTHHN/THWN-2 (1)3AWGTHHN/THWN-2 (1)8AWGTHHN/THWN-2 NONE
5 1/2"EMT (2)18AWGTHHN/THWN-2 NONE NONE NONE

755 RAVENDALE DR, MOUNTAIN VIEW CA 94043

CONTRACTOR INSTALLED

LUNAR ENERGY

Phone: (650) 351-2060 Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

STAMP SPACE

Rev A DATE:11 June 2026

Reviewed for Code Compliance

City of San Jose, Building Division Building Electrical Plumbing Mechanical

Kiet Pham (408) 535-7773

No. _____ 24-102993 Date: 07/02/2026

ELECTRICAL

ELECTRICAL

PV4.0


MAX AC CURRENT NOM. AC VOLTAGE MAX POWER (AC) CURRENT MAX INPUT 9.6KW [240V] [SI1-SB]MODEL MAKE INVERTERS RATING

INVERTERS RATING
MAKE LUNAR ENERGY
MODEL 9.6KW [240V] [SI1-SB]
MAX INPUT CURRENT 37.5A
MAX POWER(AC) 9600W
NOM. AC VOLTAGE 240V
MAX AC CURRENT 40A
CEC EFFICIENCY 95.5%
CONDUCTOR SIZING CALCULATIONS
CIRCUIT DESCRIPTION CURRENT Imax(690.8(A)(3)) Icont(690.8(B)(1)calc) SPECIFIED CONDUCTOR AMPACITY@90c AMBIENT TEMP c CURRENT CARRYING COND. COND.OF USE APPLIED(690.8(B)(2)calc
PV SOURCE CIRCUIT STRING A-B 16A 16A 16Ax1.25=20A #10THWN-2 40A 31-35 4-6 40Ax0.96(amb.temp)x0.8(raceway fill)=30.72A>Imax
INVERTER AC OUTPUT 40A 40A 40A Imaxx1.25=50A #8THWN-2 55A 31-35 1-3 55Ax0.96(amb.temp.)x1(raceway fill)=52.8A>Imax
LUNAR HUB GRID IN/OUT 100A 100A 100A #3THWN-2 115A 31-35 1-3 115Ax0.96(amb.temp.)x1(raceway fill)=110.4A>100A
BATTERY RATINGS
MAKE LUNAR ENERGY
MODEL L2-ESS-20KWH
Total Energy[kWh] 20
Max Load Start Capability 134LRA
TERMINAL TEMPERATURE RATING CONSIDERATIONS
CIRCUIT DESCRIPTION CURRENT Icont TERMINAL TEMP RATING SPECIFIED CONDUCTOR AMPACITY @ TERMNAL TEMP. RATING
PV SOURCE CIRCUIT STRING A-B 16A 16A x 1.25=20A 75C #10 35A
INVERTER AC OUTPUT 40A 40A Imaxx1.25=50A 75C #8 50A
LUNAR HUB GRID IN/OUT 100A 100A 75C #3 100A
VOLTAGE DROP CALCULATIONS
LENGTH I Ohms/kFt V CALC Vdrop
50Ft 16A 0.9989 450V 50' x 16A x 2 x 0.9989/1000'/450V= 0.36%
50Ft 16A 0.9989 450V 50' x 16A x 2 x 0.9989/1000'/450V= 0.36%
30Ft 40A 0.6282 240V 30' x 40A x 2 x 0.6282/1000'/240V= 0.63%
MODULE AND ARRAY RATINGS:(18) MODULES)
SOLAR MODULE RATINGS(STC) STRING A STRING B
MAKE LG SERIES 9 9
MODEL LG370N1K-A6 PARALLEL 1 1
Imp 10.43A Imp 7.4A 7.4A
Vmp 35.5V Vmp 450V 450V
Isc 10.96A Isc 16A 16A
Voc 41.9V Voc 450V 450V
Pmax 370W Pmax 3330W 3330W
%Voc/C -0.26%
CONDUIT SCHEDULE*ALL WIRE ASSUMED TO BE CU UNLESS OTHERWISE SPECIFIED
GROUND
# CONDUIT CONDUCTOR(RED/BLACK) NEUTRAL(WHITE) (GREEN) (BARE COPPER)
1 NONE (2)10AWG PVWIRE NONE NONE (1)6AWG
2 3/4"EMT (4)10AWGTHHN/THWN-2 NONE (1)10AWGTHHN/THWN-2 NONE
3 3/4"EMT (2)8AWGTHHN/THWN-2 (1)8AWGTHHN/THWN-2 (1)10AWGTHHN/THWN-2 NONE
4 1"EMT (2)3AWGTHHN/THWN-2 (1)3AWGTHHN/THWN-2 (1)8AWGTHHN/THWN-2 NONE
5 1/2"EMT (2)18AWGTHHN/THWN-2 NONE NONE NONE

CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW,

CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance

City of San Jose, Building Division Building Electrical Plumbing Mechanical Kiet Pham (408) 535-7773

No. 24-102993 Date: 07/02/2026


STRING A, ARRAY 1 & 2 (1) STRING OF (9) MODULES (9) LUNAR MAXIMIZER OPTIMIZER UNITS (9) LG LG370N1K-A6 (370W) MODULES STRING B, ARRAY 2 (1) STRING OF (9) MODULES (9) LUNAR MAXIMIZER OPTIMIZER UNITS (9) LG LG370N1K-A6 (370W) MODULES SYSTEM SIZE: 6660W DC, 9600W AC & ESS 20 kWh (AC)

ALL CONDUCTORS AND TERMINATIONS SHALL BE AT THE MAIN PANEL, GEC WILL BE SIZED AS #6 AWG EXCEPTION: WHEN ESTABLISHING NEW GROUND SIZE GEC FROM PANEL GROUND BAR TO

LISTED FOR 75 DEGREES. CU PER 250.66 (A) ROD/UFER PER 250.52 SIZE EGC PER 250.122 GROUNDING NOTES:

LUNAR BATTERY PACK 20KWH (STACK OF4 BATTERY MODULES WITH 9.6KW INVERTER)

(N) CONNECTDER ISLANDER (METER SOCKET ADAPTER)

(1) 8 AWG THHN/THWN-2 NEUTRAL (WHITE) *ALL WIRE ASSUMED TO BE CU UNLESS OTHERWISE SPECIFIED

B. SIZE GEC FROM PANEL GROUND BAR TO GROUND

GROUNDING NOTES:

C. ROD/UFER PER 250.52

A. SIZE EGC PER 250.122

THHN/THWN-2 (1) 10 AWG THHN/THWN-2 (1) 10 AWG 120/240VAC, 1PH END FED 200A MAIN BREAKER 225A BUSBAR SERVICE PANEL

CONDUIT SCHEDULE*ALL WIRE ASSUMED TO BE CU UNLESS OTHERWISE SPECIFIED
GROUND
# CONDUIT CONDUCTOR(RED/BLACK) NEUTRAL(WHITE) (GREEN) (BARE COPPER)
1 NONE (2)10AWG PVWIRE NONE NONE (1)6AWG
2 3/4"EMT (4)10AWGTHHN/THWN-2 NONE (1)10AWGTHHN/THWN-2 NONE
3 3/4"EMT (2)8AWGTHHN/THWN-2 (1)8AWGTHHN/THWN-2 (1)10AWGTHHN/THWN-2 NONE
4 1/2"EMT (2)18AWGTHHN/THWN-2 NONE NONE NONE

CONTRACTOR INSTALLED

LUNAR ENERGY 755 RAVENDALE DR, MOUNTAIN VIEW, CA 94043 Phone: (650) 351-2060 Email:ekaneko@lunarenergy.com

Rev A DATE:11 June 2026

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

STAMP SPACE

Reviewed for Code Compliance City of San Jose, Building Division X Building □ Electrical □ Plumbing □ Mechanical Kiet Pham (408) 535-7773 No. 24-102993 Date: 07/02/2026

ELECTRICAL

PV4.2


Capability Max Load Start Total Energy [kWh] MODEL MAKE BATTERY RATINGS CEC EFFICIENCY MAX AC CURRENT NOM. AC VOLTAGE MAX POWER (AC) CURRENT MAX INPUT 9.6KW [240V] [SI1-SB]MODEL MAKE INVERTERS RATING

BATTERY RATINGS
MAKE LUNAR ENERGY
MODEL L2-ESS-20KWH
Total Energy[kWh] 20
Max Load Start Capability 134LRA
CONDUCTOR SIZING CALCULATIONS
CIRCUIT DESCRIPTION CURRENT Imax(690.8(A)(3)) Icont(690.8(B)(1)calc) SPECIFIED CONDUCTOR AMPACITY@90c AMBIENT TEMP c CURRENT CARRYING COND. COND.OF USE APPLIED(690.8(B)(2)calc)
PV SOURCE CIRCUIT STRING A-B 16A 16A 16Ax1.25=20A #10THWN-2 40A 31-35 4-6 40Ax0.96(am b.temp)x0.8(raceway fill)=30.72A>Imax
INVERTER AC OUTPUT 40A 40A 40A Imaxx1.25=50A #8THWN-2 55A 31-35 1-3 55Ax0.96(am b.temp.)x1(raceway fill)=52.8A>Imax
TERMINAL TEMPERATURE RATING CONSIDERATIONS
CIRCUIT DESCRIPTION CURRENT Icont TERMINAL TEMP RATING SPECIFIED CONDUCTOR AMPACITY @ TERMNAL TEMP. RATING
PV SOURCE CIRCUIT STRING A-B 16A 16A x 1.25=20A 75C #10 35A
INVERTER AC OUTPUT 40A 40A Imaxx1.25=50A 75C #8 50A

CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance

City of San Jose, Building Division Building Electrical Plumbing Mechanical Kiet Pham (408) 535-7773

No. 24-102993 Date: 07/02/2026

ELECTRICAL

PV4.3


INSTALL ON THE UTILITY METER

WARNING

THIS SERVICE METER IS ALSO SERVED BY A PHOTOVOLTAIC SYSTEM

INSTALL ON THE MAIN BREAKER PANEL

PHOTOVOLTAIC SYSTEM AC DISCONNECT

OPERATING VOLTAGE 240 VOLTS OPERATING CURRENT 48 AMPS

CAUTION TRI POWER SOURCE SECOND SOURCE IS PHOTOVOLTAIC SYSTEM THIRD SOURCE IS ENERGY STORAGE SYSTEM

OPERATING CURRENT OPERATING VOLTAGE 240 VOLTS AC DISCONNECT PHOTOVOLTAIC SYSTEM

TRI POWER SOURCE CAUTION

OPERATING VOLTAGE 240 VOLTS OPERATING CURRENT 48 AMPS

RAPID SHUTDOWN SOLAR PV SYSTEM AMPS INSTALL ON THE INVERTER SOLAR PV SYSTEM RAPID SHUTDOWN

SOLAR ELECTRIC EQUIPPED WITH SWITCH FOR

WARNING: PHOTOVOLTAIC OF EXTERIOR CONDUIT BENDS ALL EXTERIOR CONDUIT. INSTALL WITHIN 12 INCHES INSTALL TO BE INSTALLED ON EVERY 10 FEET ON LOAD SIDES MAY BE ENERGIZED TERMINALS ON BOTH THE LINE AND ELECTRIC SHOCK HAZARD

THIS SERVICE METER WARNING

AC DISCONNECT PHOTOVOLTAIC SYSTEM INSTALL ON THE PV AC DISCONNECT

MAX SYSTEM VOLTAGE 600 VDC

PHOTOVOLTAIC SYSTEM

OPERATING CURRENT
OPERATING VOLTAGE
DC DISCONNECT INSTALL ON THE INVERTER

CONTRACTOR INSTALLED

LUNAR ENERGY 755 RAVENDALE DR, MOUNTAIN VIEW, CA 94043 Phone: (650) 351-2060 Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A DATE:11 June 2026

STAMP SPACE

WARNING LABELS

PV 5.0


  1. WATERPROOFING BY CONTRACTOR

| PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: WOOD STUD WALL MOUNTING DETAIL | DATE:

2/11/26 | | --- | --- | --- | | | | SHEET NUMBER: S1.0 |

CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW,

CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A

DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance

City of San Jose, Building Division Building Electrical Plumbing Mechanical

Kiet Pham (408) 535-7773

No. 24-102993 Date: 07/02/2026

BATTERY MOUNTING DETAILS

PV 6.0


| PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: CONCRETE WALL MOUNTING DETAIL | DATE:

2/11/26 | | --- | --- | --- | | PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: CONCRETE WALL MOUNTING DETAIL | SHEET NUMBER: S1.1 |

CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW,

CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A

DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance

City of San Jose, Building Division Building Electrical Plumbing Mechanical Kiet Pham (408) 535-7773

No. 24-102993 Date: 07/02/2026

BATTERY MOUNTING DETAILS

PV 6.1


CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW,

CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A

DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance

City of San Jose, Building Division Building Electrical Plumbing Mechanical Kiet Pham (408) 535-7773

No. 24-102993 Date: 07/02/2026

BATTERY MOUNTING DETAILS

PV 6.2


STEP 1 - INSTALL HORIZONTAL UNISTRUT SUPPORT RAIL

STEP 2 - INSTALL VERTICAL UNISTRUT MOUNTING RAIL

STEP 3 - SEE DETAIL S2.1

  1. WATERPROOFING BY CONTRACTOR

| AO structures | PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: WOOD STUD WALL MOUNTING DETAIL AT (3) STUD CONDITION | DATE:

2/11/26 | | --- | --- | --- | --- | | | | | SHEET NUMBER: S2.0 |

CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW,

CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A

DATE:11 June 2026

STAMP SPACE

Reviewed for Code Compliance City of San Jose, Building Division Building Electrical Plumbing Mechanical Kiet Pham (408) 535-7773 No._____24-102993 Date: 07/02/2026

BATTERY MOUNTING DETAILS

PV 6.3


STEP 3 - INSTALL MANUFACTURER MOUNTING BRACKET/BATTERY ASSEMBLY

LUNAR LFP BATTERY ANCHORAGE

CONTRACTOR INSTALLED

LUNAR ENERGY

755 RAVENDALE DR, MOUNTAIN VIEW,

CA 94043

Phone: (650) 351-2060

Email:ekaneko@lunarenergy.com

PROJECT NAME: SAN JOSE BATTERY MASTERFILE

Rev A DATE:11 June 2026

STAMP SPACE

BATTERY MOUNTING DETAILS

PV 6.4


February 26, 2026

TO: Lunar Energy

SUBJECT: Lunar Battery Anchorage - California Fully Wall Mounted System

SCOPE OF WORK:

AOstructures, Inc. was asked to provide the structural anchorage design for a Lunar LFP Battery System. The installation method consists of a Lunar Battery System that is fully hung from an existing wall. The wall may be either of the following below conditions:

● Wood framed wall consisting of typical 2x4 (minimum) studs @ 16" o.c.

$$ 0c1ast66\ c. $$

● Wood framed wall consisting of atypical 2x4 (minimum) stud spacing

● Concrete wall, 6" minimum thickness with f'c = 2,500 psi, min.

● CMU wall, fully grouted, normal weight CMU

The wall anchorage is designed to resist both the dead weight (downward load) of the equipment as well as the vertical and lateral seismic forces (vertical, horizontal and withdrawl).

ESS DESCRIPTION

The subject battery system consists of a modular design which includes (1) inverter and can include as few as (2) battery blocks (10kWh ESS) and as many as (6) battery blocks (30kWh ESS). Each of the modular elements are attached modularly to a wall mounting bracket provided by the manufacturer. The bottom wall mounting bracket is fastened to the wall using (4) fasteners with additional modular elements above clipped to the bracket below and fastened to the wall using (2) additional fasteners. For the 10kWh ESS, there are a total of (8) fasteners while the 30 kWh ESS utilizes (16) fasteners. See Mechanical properties of the modular battery system, below:

Mechanical 10kWh 15kWh 20kWh 25kWh 30kWh
Dimensions(LxWxD) 34.8"x24.4"x13.5"(884x619x344mm) 45.5"x24.4"x13.5"(1156x619x344mm) 56.1"x24.4"x13.5"(1425x619x344mm) 66.8"x24.4"x13.5"(1696x619x344mm) 77.4"x24.4"x13.5"(1967x619x344mm)
Dimensions(LxWxD) Inverter:12"x24.4"x13.5"(305x619x344mm)Top+BottomCover:3"x24.4"x13.5"(75x619x344mm)
Inverter Mass 42lb(19kg)
Total Assembly Mass(包括 brackets& covers) 305lb(139kg) 421lb(191kg) 540lb(245kg) 659lb(299kg) 778lb(354kg)
Mounting Floor or wall mounted

Reviewed for Code Compliance City of San Jose, Building Division □X Building □ Electrical □ Plumbing □ Mechanical Kiet Pham (408) 535‐7773 24-102993 07/02/2026No.

LIMITATIONS:

The scope of this report is strictly limited to the anchorage of the above specified wall mounting brackets to the existing wall framing only. No evaluation of the existing structure or any of the manufacturer provided elements (i.e. batteries/inverters/mounting brackets/clips/base/etc.) is included or implied in the scope of this report. The calculations that follow are designed with the following design criteria and are only applicable for sites with design criteria less than that specified below: 2.26.26 - Lunar Battery Anchorage Certification.xlsx 1

PC 24-102993 MASTER FILE


DESIGN CRITERIA:

● Applicable Codes = 2025 CBC, ASCE 7-22

● Risk Category II

● Seismic: Sds = 2g, Ip = 1, Rµ = 1.3, Car =1, Rpo = 1.5

EQUIPMENT SPECIFICATIONS:

● Equipment:

● All equipment shall be installed per manufacturer specifications

CONCLUSIONS:

Anchorage to wood framed wall construction:

Each modular mounting bracket shall be attached to the existing framing using a minimum of (2) 1/4"Ø Lag Screw fasteners installed into (2) different existing 2x studs to suspend the equipment above grade. (4) fasteners shall be used for the bottom bracket. The fasteners shall be installed at manufacturer provided mounting holes and shall be installed within the middle 1/3 of the stud width with a minimum threaded embedment of 2.0'' into the existing wood stud framing in the wall (See Detail S1.0).

This proposed mounting method assumes that only one ESS is mounted per pair of studs. In some cases, the contractor may consider mounting multiple ESS's per pair of studs. Examples of such conditions are provided below. In all cases, it is recommended that the contractor contact a licensed engineer to evaluate the proposed existing stud wall to assess it's suitabilty to support the weight of multiple ESS's.

● Walls < 10'-0 tall with 2x6 studs or larger

● Walls < 12'-0 tall with 2x8 studs or larger

● Bearing walls with minimal (i.e. < 8'-0") tributary area of loads.

$$ 1.e.<8^{\prime}-0^{n}) $$

● Walls that are sheathed with OSB or CDX plywood intended to resist lateral forces (shear walls)

In some conditions, such as irregular stud spacing or stud spacing that exceeds 16" o.c., the as-built stud spacing may not support the pre-drilled manufacturer mounting hole locations without a supplemental support. Details S2.0 and S2.1 are provided to propose an alternative mounting solution for such conditions and provide flexibility for the installation when preferred.

$$ 16^{n},0. $$

Anchorage to concrete or CMU wall construction:

Each modular mounting bracket shall be attached to the existing wall using a minimum of (2) 1/4 diameter Hilti Kwik HUS-EZ or Simpson Titen HD fasteners with a minimum embedment of 2'' into the supporting concrete (See Detail S1.1) or CMU (See Detail S1.2) wall. The fasteners shall be installed at all manufacturer provided mounting hole locations. If mounted in an exterior or otherwise corrosive environment, the fasteners shall be galvanized or stainless steel. The fasteners shall maintain a minimum 6" edge and/or end distance from concrete and/or CMU wall ends/edges. Fasteners installed in CMU walls shall maintain a 2.5" separation from grout head joints.

Please contact me with any further questions or concerns regarding this project.

Sincerely,

Reviewed for Code Compliance

City of San Jose, Building Division

□X Building

□ Electrical

□ Plumbing

□ Mechanical

Kiet Pham (408) 535‐7773

24-102993 07/02/2026


NOTES: [#]

  1. FOR EXTERIOR ENVIRONMENTS, USE STAINLESS STEEL FASTENERS & GALVANIZED STRUT

  2. SEE MANUFACTURER INSTALLATION INSTRUCTIONS

  3. WATERPROOFING BY CONTRACTOR

| AO structures | PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: WOOD STUD WALL MOUNTING DETAIL | DATE:

2/11/26 | | --- | --- | --- | --- | | AO structures | | | SHEET NUMBER: S1.0 |


NOTES: [#]

  1. FOR EXTERIOR ENVIRONMENTS, USE STAINLESS STEEL FASTENERS & GALVANIZED STRUT

  2. SEE MANUFACTURER INSTALLATION INSTRUCTIONS

  3. WATERPROOFING BY CONTRACTOR

| AO structures | PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: CONCRETE WALL MOUNTING DETAIL | DATE:

2/11/26 | | --- | --- | --- | --- | | AO structures | | | SHEET NUMBER: S1.1 |


  1. SEE MANUFACTURER INSTALLATION INSTRUCTIONS

  2. WATERPROOFING BY CONTRACTOR

| AO structures | PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: CMU WALL MOUNTING DETAIL | DATE:

2/11/26 | | --- | --- | --- | --- | | AO structures | | | SHEET NUMBER: S1.2 |


STEP 1 - INSTALL HORIZONTAL UNISTRUT SUPPORT RAIL

STEP 2 - INSTALL VERTICAL UNISTRUT MOUNTING RAIL

STEP 3 - SEE DETAIL S2.1

  1. FOR EXTERIOR ENVIRONMENTS, USE STAINLESS STEEL FASTENERS & GALVANIZED STRUT

  2. SEE MANUFACTURER INSTALLATION INSTRUCTIONS

  3. WATERPROOFING BY CONTRACTOR

| PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: WOOD STUD WALL MOUNTING DETAIL AT (3) STUD CONDITION | DATE:

2/11/26 | | --- | --- | --- | | PROJECT: LUNAR LFP BATTERY ANCHORAGE | SHEET TITLE: WOOD STUD WALL MOUNTING DETAIL AT (3) STUD CONDITION | SHEET NUMBER: S2.0 |


STEP 3 - INSTALL MANUFACTURER MOUNTING BRACKET/BATTERY ASSEMBLY

| NOTES: [#]

  1. FOR EXTERIOR ENVIRONMENTS, USE STAINLESS STEEL FASTENERS & GALVANIZED STRUT
  2. SEE MANUFACTURER INSTALLATION INSTRUCTIONS
  3. WATERPROOFING BY CONTRACTOR
    PROJECT:
    LUNAR LFP BATTERY
    ANCHORAGE SHEET TITLE:
    WOOD STUD WALL MOUNTING
    DETAIL AT (3) STUD CONDITION DATE:
    2/11/26 SHEET NUMBER:
    S2.1

Input Variables
Per ASCE 7-22, Chapter 13
Fp-Wall Mounted Equipment
Equipment Label 1
Equipment Name Lunar LFP Battery-10kWh
Sds= 2.00g (Section11.4.5)
Importance Factor(lp)= 1.00 (Section13.1.3)
z/h= 0.50
Hf= 2.25 (13.3.1.1)
Rμ= 1.30 (13.3.1.2)
Car= 1.0 (Table13.6-1)
Rpo= 1.5 (Table13.6-1)
Equipment Weight(Wp)= 305Jb

Seismic Design Force

$$ \begin{array}{r l r}{\mathsf{F p}=}\end{array} $$

(13.3-1)

$$ =,282,1
$$

Governs

$$ {\sf{F P}}\ (\sf{m a x})= $$

(13.3-2)

$$ \begin{array}{l} F p (\min ) = 0. 3 * S d s * I p * W p \ = 1 8 3 \mathrm {I b} \ \end{array} $$

(13.3-3)

Fp = 282 lb (ultimate)

Seismic Forces Required for Anchorage to Concrete/Masonry

$\Omega$o = 2.0 (Used for anchorage to concrete)
$\Omega$o Fp = 0,563 lb (ultimate)
Seismic Design Force(Vertical Load)
Fp(vert)= 0.2SdsWp
=122lb
Fp(vert)= 122lb (ultimate)

$$ \begin{array}{r l}{\mathsf{F p},(\mathsf{v e r t})=}&{{}0.2^{\star},\mathsf{S d s\ }{}^{\star},\mathsf{W p}}\ {}&{{}=\ 122,10}\end{array} $$

Note: Use 244 lb for anchorage forces at concrete/masonry


Fastener (to Wood Framed Wall) Capacity Check - Shear and Withdrawl - Lunar LFP Battery - 10kWh

Demand Loads
Equipment Weight= 305 lb (Per manufacturer)
Vertical Seismic Force Demand= 122 lb (See Fp Calcs)
Lateral Shear Demand= 282 lb (See Fp Calcs)
1.0D+0.7Ev+0.7Eh= 391lb vertical 198lb horizontal
0.6D-0.7Ev+0.7Eh= 98lb vertical 198lb horizontal
Fastener Selection
Fastener= 1/4"Ø Lag Screw
Number of Fasteners= 8
Stud Width= 1.500 in in
Required Edge Distance= 0.625 in in (2.5*d as per NDS)
2x Edge Distance+Fastener Diameter= 1.500 in in ≤stud width,OK!

Fastener Withdrawl Capacity Check (Seismic force away from the wall)

Fastener Withdrawl Capacity Check(Seismic force away from the wall)
Withdrawl Shear Force= 198 lb (ASD)
Embedment Depth= 2.0 in
Pullout Capacity Per Inch= 173 lb (G=0.42-per NDS)
Group Fastener Withdrawl Capacity= 2768 lb
w/Cd of 1.6= 4429 lb
4429 lb capacity>198lb demand Therefore,OK 4.5% stress
Fastener Shear Capacity Check(Left Right Force)
Lateral Shear Demand= 198 lb
Individual Fastener Shear Capacity= 120 lb (Z1per NDS w/12 gage mounting bracket)
Group Fastener Shear Capacity= 960 lb
Group Shear Capacityw/Cd=1.6= 1536 lb
1536lb capacity>198lb demand Therefore,OK 12.9% stress
Fastener Shear Capacity Check(Up Down Force)
Vertical Shear Demand= 391lb (1.0D+0.7Ev)
Individual Fastener Shear Capacity= 160lb (Z
Group Fastener Shear Capacity= 1280lb
Group Shear Capacity w/Cd=1.6= 2048lb
2048lb capacity>391lb demand Therefore,OK 19.1% stress
Check Combined Loading
Withdrawl Stress = 5%
Max Shear Stress = 19%
Combined Stress = 20%

Results: (8) 1/4"Ø Lag Screw(s) have a combined stress ratio of 20%, OK!


Input Variables
Per ASCE 7-22, Chapter 13
Fp - Wall Mounted Equipment
Equipment Label 1
Equipment Name Lunar LFP Battery - 30kWh
Sds= 2.00g (Section 11.4.5)
Importance Factor(lp)= 1.00 (Section 13.1.3)
z/h= 0.50
Hf= 2.25 (13.3.1.1)
Rμ= 1.30 (13.3.1.2)
Car= 1.0 (Table 13.6-1)
Rpo= 1.5 (Table 13.6-1)
Equipment Weight(Wp)= 778Jb

Seismic Design Force

$$ \begin{array}{r l r}{\mathsf{F}!{\sf P}=}&{{}}\end{array} $$

(13.3-1)

$$ =718,15 $$

Governs

$$ {\sf{F P}}\ (\sf{m a x})= $$

(13.3-2)

$$ {\sf F p},(\sf{m i n})=\qquad\qquad\qquad\qquad\qquad\qquad\qquad\qquad\qquad\qquad\qquad\qquad\qquad\qquad $$

(13.3-3)

Fp = 718 lb (ultimate)

Seismic Forces Required for Anchorage to Concrete/Masonry

$\Omega$o = 2.0 (Used for anchorage to concrete)
$\Omega$o Fp= 1,436 lb (ultimate)
Seismic Design Force(Vertical Load)
Fp(vert)= 0.2SdsWp
=311lb
Fp(vert)= 311lb(ultimate)

$$ \begin{array}{r l}{\mathsf{F p},(\mathsf{v e r t})=}&{{}\quad0.2^{\star},\mathsf{S d s\ }{}^{\star},\mathsf{W p}}\ {}&{{}=\ 311,110}\end{array} $$

Note: Use 623 lb for anchorage forces at concrete/masonry


Fastener (to Wood Framed Wall) Capacity Check - Shear and Withdrawl - Lunar LFP Battery - 30kWh

Demand Loads
Equipment Weight= 778 lb (Per manufacturer)
Vertical Seismic Force Demand= 311 lb (See Fp Calcs)
Lateral Shear Demand= 718 lb (See Fp Calcs)
1.0D+0.7Ev+0.7Eh= 996lb vertical 503lb horizontal
0.6D-0.7Ev+0.7Eh= 249lb vertical 503lb horizontal
Fastener Selection
Fastener = 1/4"Ø Lag Screw
Number of Fasteners = 16
Stud Width = 1.500 in in
Required Edge Distance = 0.625 in in (2.5*d as per NDS)
2x Edge Distance + Fastener Diameter = 1.500 in in ≤ stud width, OK!
Fastener Withdrawl Capacity Check(Seismic force away from the wall)
Withdrawl Shear Force= 503 lb (ASD)
Embedment Depth= 2.0 in
Pullout Capacity Per Inch= 173 lb (G=0.42-per NDS)
Group Fastener Withdrawl Capacity= 5536 lb
w/Cd of 1.6= 8858 lb
8858 lb capacity>503lb demand Therefore,OK 5.7% stress
Fastener Shear Capacity Check(Left Right Force)
Lateral Shear Demand= 503 lb
Individual Fastener Shear Capacity= 120 lb (Z1per NDS w/12 gage mounting bracket)
Group Fastener Shear Capacity= 1920 lb
Group Shear Capacityw/Cd=1.6= 3072 lb
3072lb capacity>503lb demand Therefore,OK 16.4% stress
Fastener Shear Capacity Check(Up Down Force)
Vertical Shear Demand= 996 lb (1.0D+0.7Ev)
Individual Fastener Shear Capacity= 160 lb (Z
Group Fastener Shear Capacity= 2560lb
Group Shear Capacityw/Cd=1.6= 4096lb
4096lb capacity>996lb demand Therefore,OK 24.4% stress
Check Combined Loading
Withdrawl Stress = 6%
Max Shear Stress = 24%
Combined Stress = 26%

Results: (16) 1/4"Ø Lag Screw(s) have a combined stress ratio of 26%, OK!


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

Company: Page: 1
Address: Specifier:
Phone I Fax: E-Mail:
Design: Lunar ESS - Concrete Anchorage Date: 1/20/2026
Fastening point:

Specifier's comments:

1 Input data

Anchor type and diameter: KWIK HUS-EZ(KH-EZ)-SS316 1/4(15/8)
Item number: 2245630 KH-EZ SS316 1/4"x2"
Specification text: Hilti∅1/4in KWIK HUS-EZ(KH-EZ)-SS316 with 1.625 in nominal embedment depth per ICC-ES ESR-3027,Hammer drill bit installation per MPII
Effective embedment depth: hef,act=1.190in,hnom=1.625in.
Material: AISI316
Evaluation Service Report: ESR-3027
Issued I Valid: 12/1/2023
Proof: Design Method ACI318-19/Mech
Shear edge breakout verification: Row closest to edge(Case3only fromACI318-19Fig.R.17.7.2.1b)
Stand-off installation: eb=0.000in.(no stand-off);t=0.250in.
Anchor plate$ ^{R}$ : lx x ly x t=77.400in.x24.400in.x0.250in.;(Recommended plate thickness:not calculated)
Profile: no profile
Base material: cracked concrete,2500,f c =2,500psi:h=6.000in.
Installation: Hammer drilled hole,Installation condition:Dry
Reinforcement: tension:not present,shear:not present;no supplemental splitting reinforcement present edge reinforcement:none or<No.4bar
Seismic loads(cat.C,D,E,orF) Tension load:yes(17.10.5.3(d)) Shear load:yes(17.10.6.3(c))

R

Geometry [in.] & Loading [lb, in.lb]


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

www.hilti.com

Company: Page: 2
Address: Specifier:
Phone I Fax: E-Mail:
Design: Lunar ESS-Concrete Anchorage Date: 1/20/2026
Fastening point:

1.1 Unfactored loads

Sustained load factor Load factor $ f_{1} $ or $ f_{2}$ $ V_{x} $ [lb] $ V_{y} $ [lb] N[lb] $ M_{x} $ [in.lb] $ M_{y} $ [in.lb] $ M_{z} $ [in.lb]
D(Dead) 1.000 - 778 - - - - -
F(Fluid) 1.000 - - - - - - -
T(Temperature) 1.000 - - - - - - -
L(Live) 1.000 0.500 - - - - - -
H(Lateral) 1.000 - - - - - - -
$ L_{r} $ (Roof live) 1.000 - - - - - - -
S(Snow) 1.000 0.200 - - - - - -
R(Rain) - - - - - - - -
W(Wind) - - - - - - - -
E(Earthquake) - - 623 1,436 1,436 - - -

1.2 Load combination and design results

1.2.1 Load combination

1.2.2 Design results

Case Description Forces [lb] / Moments [in.lb] Seismic Max. Util. Anchor[%]
Equation(16-1) 1.4(D+F) N=0;Vx=1,089;Vy=0;Mx=0;My=0;Mz=0; yes 27
Equation(16-5) 1.2(D+F)+1.0(E)+f1L+1.6(H)+f2S N=1,436;Vx=1,557;Vy=1,436;Mx=0;My=0;Mz=0; yes 72
Equation(16-7) 0.9(D+F)+1.0(E)+1.6(H) N=1,436;Vx=1,323;Vy=1,436;Mx=0;My=0;Mz=0; yes 68

$$ \mathsf{N}=0;\mathsf{V}{x}=1,089;\mathsf{V}{y}=0; $$

$$ \mathsf{M}{x}=0;\mathsf{M}{y}=0;\mathsf{M}_{z}=0; $$

$$ N=1.436:V=1.557:V=1.436 $$

$$ M_{x}=0;M_{x2}=0;M_{2}=0; $$

$$ \ \ N{=11,436;mathbb V{{x}}}=1,323;\mathbb{V}{y_y}=1,436; $$

$$ \mathsf{M}{x}=0;\mathsf{M}{y}=0;\mathsf{M}_{z}=0; $$


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

2 Proof I Utilization(Governing Cases)
Design values[lb] Utilization
Loading Proof Load Capacity βN/βV[%] Status
Tension Pullout Strength 90 161 56/- OK
Shear Concrete edge failure in direction x+ 2,118 4,061 -/53 OK
Loading βN βV ζ Utilization βN,V[%] Status
Combined tension and shear loads 0.558 0.521 5/3 72 OK

$$ \ N,,{V},[9/0] $$

$$ \beta_{N} $$

$$ \beta_v $$

3 Warnings

• Please consider all details and hints/warnings given in the detailed report!

Fastening meets the design criteria!


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

Company: Page: 4
Address: Specifier:
Phone I Fax: E-Mail:
Design: Lunar ESS-Concrete Anchorage Date: 1/20/2026
Fastening point:

4 Remarks; Your Cooperation Duties

• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application.

• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you.


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

Company: Page: 1
Address: Specifier:
Phone I Fax: E-Mail:
Design: Masonry-Jan 20,2026 Date: 1/20/2026
Fastening point:

Specifier's comments:

1 Input data

Anchor type and diameter: KWIK HUS-EZ (KH-EZ)-SS316 1/4(21/2)
Item number: 2245632 KH-EZ SS316 1/4"x2-1/2"
Specification text: Hilti Ø1/4(21/2)KWIK HUS-EZ(KH-EZ)-SS316 with 1.93 in nominalembedment depth per ICC-ES ESR-3056,Hammer drilled installation per MPII
Effective embedment depth: hef=1.930in.
Material: AISI 316
Evaluation Service Report: ESR-3056
Issued I Valid: 10/1/2024
Proof: Design Method LRFD(AC01)Masonry+ACI318-19
Stand-off installation: eb=0.000in.(no stand-off);t=0.118in.
Anchor plate$ ^{R}$ : lx x ly x t=6.000in.x6.000in.x0.118in.;(Recommended plate thickness:not calculated)
Profile: no profile
Base material: uncracked Grout-filled CMU,f=1500,f=1,500psi,LxWxH:16.000in.x8.000in.x8.000in.;Solid Head Joint:no;open ended unit:noJoints:vertical:0.375in.;horizontal:0.375in.
Installation: Face installation,Drill hole:Hammer drilled,Installation condition:Dry
Seismic loads(cat.C,D,E,或F) Tension load:yes(17.10.5.3(d))Shear load:yes(17.10.6.3(c))

R

Geometry [in.]


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

Company: Page: 2
Address: Specifier:
Phone I Fax: E-Mail:
Design: Masonry-Jan 20,2026 Date: 1/20/2026
Fastening point:

Geometry [in.] & Loading [lb, in.lb]

1.1 Unfactored loads

Sustained load factor Load factor $ f_{1} $ or $ f_{2}$ $ V_{x} $ [lb] $ V_{y} $ [lb] N[lb] $ M_{x} $ [in.lb] $ M_{y} $ [in.lb] $ M_{z} $ [in.lb]
D(Dead) 1.000 - - -48 - - - -
F(Fluid) 1.000 - - - - - - -
T(Temperature) 1.000 - - - - - - -
L(Live) 1.000 0.500 - - - - - -
H(Lateral) 1.000 - - - - - - -
$ L_{r} $ (Roof live) 1.000 - - - - - - -
S(Snow) 1.000 0.200 - - - - - -
R(Rain) - - - - - - - -
W(Wind) - - - - - - - -
E(Earthquake) - - 90 -39 90 - - -

$$ \underline{{_{\chi}}} $$

$$ \ {tt V_{x}}[{\ !{\tt b b}}] $$

1.2 Load combination and design results

1.2.1 Load combination

Load case Load combination
Equation(16-1) 1.4(D+F)
Equation(16-5) 1.2(D+F)+1.0(E)+f1L+1.6(H)+f2S
Equation(16-7) 0.9(D+F)+1.0(E)+1.6(H)

$$ 1.4\ (\mathsf{D}+\mathsf{F}) $$

$$ \sf{E q u a t i o n\ (6\ -5)}\qquad\textstyle1.2\ (D+F)+\ .1.0\ (E)+f_{1}L+1.6\ (H)+f_{2}S $$

$$ \sf{E q u a t i o n~(6-7)}\qquad\quad0.9\ (D+F)+1.0\ (E)+1.6\ (H) $$


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

www.hilti.com

1.2.2 Design results
Case Description Forces [lb] / Moments[in.lb] Seismic Max. Util. Anchor[%]
Equation(16-1) 1.4(D+F) N=0;Vx=0;Vy=-67;Mx=0;My=0;Mz=0; yes 8
Equation(16-5) 1.2(D+F)+1.0(E)+f1L+1.6(H)+f2S N=90;Vx=90;Vy=-97;Mx=0;My=0;Mz=0; yes 65
Equation(16-7) 0.9(D+F)+1.0(E)+1.6(H) N=90;Vx=90;Vy=-82;Mx=0;My=0;Mz=0; yes 65

$$ N = 0; V _ {x} = 0; V _ {v} = - 6 7; $$

$$ \mathsf{M}{x}=0;\mathsf{M}{y}=0;\dot{\mathsf{M}}_{z}=0; $$

$$ N=90;V_{x}=90;V_{y}=-97; $$

$$ \mathsf{M}{x}=0;\mathsf{M}{y}=0;\dot{\mathsf{M}}_{z}=0; $$

$$ N=90;V_{x}=90;V_{v}=-82 $$

$$ M_{x}=0:M_{x}=0:M_{z}=0 $$


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

www.mitt.com
Company: Page: 4
Address: Specifier:
Phone I Fax: E-Mail:
Design: Masonry-Jan 20,2026 Date: 1/20/2026
Fastening point:
2 Proof I Utilization(Governing Cases)
Design values[lb] Utilization
Loading Proof Load Capacity βN/βV[%] Status
Tension Pullout 90[lb] 90[lb] 64/- OK
Shear Steel 122[lb] 122[lb] -/13 OK
Loading βN βV α UtilizationβN,V[%] Status
Interaction 0.642 0.133 1.667 51 OK

$$ \ _{N}/_B,{}{[[]/]} $$

$$ \beta_ {N} $$

$$ \beta_v $$

3 Warnings

• Please consider all details and hints/warnings given in the detailed report!

Fastening meets the design criteria!


Hilti PROFIS Engineering 3.1.26

www.hilti.com www.hilti.com

Company: Page: 5
Address: Specifier:
Phone I Fax: E-Mail:
Design: Masonry-Jan 20,2026 Date: 1/20/2026
Fastening point:

4 Remarks; Your Cooperation Duties


Appendix A: Manutacurer Specifications

Mechanical 10kWh 15kWh 20kWh 25kWh 30kWh
Dimensions(LxWxD) 34.8"×24.4"×13.5"(884×619×344mm) 45.5"×24.4"×13.5"(1156×619×344mm) 56.1"×24.4"×13.5"(1425×619×344mm) 66.8"×24.4"×13.5"(1696×619×344mm) 77.4"×24.4"×13.5"(1967×619×344mm)
Dimensions(LxWxD) Inverter:12"×24.4"×13.5"(305×619×344mm)Top+BottomCover:3"×24.4"×13.5"(75×619×344mm)
InverterMass 42lb(19kg)
Total Assembly Mass(包括 brackets & covers) 305lb(139kg) 421lb(191kg) 540lb(245kg) 659lb(299kg) 778lb(354kg)
Mounting Floor or wall mounted

Appendix B: General Notes

GENERAL

● The contractor shall verify all dimensions, property setbacks, AHJ/HOA CC&R's, elevations and site conditions before starting work and shall notify AOstructure, Inc, (AOstructures) of any discrepancies.

● All report conclusions represent AOstructures, Inc.'s best professional judgment based upon industry standards.

● Resolve any conflicts on the drawings with AOstructures, Inc before proceeding with construction.

● The design criteria used for this project & listed on the first page of the report is based on the engineers best judgement and/or provided by the ATC council. AHJ specific requests may differ. Please contact our team if the design criteria needs to be modified.

● AOstructures is not responsible for enforcing safety measures or regulations. The contractor shall design, construct, and maintain all safety devices including shoring and bracing, and shall be solely responsible for conforming to all local, state and federal safety and health standards, laws and regulations. The contractor shall take necessary precautions to maintain and insure the integrity of the structure during construction. If a lawsuit is filed by one of the contractor's or subcontractor's employees, or any one else, the contractor will indemnify, defend and hold the owner and aostructures, inc harmless of any and all such claims.

● Any and all waterproofing shall be provided by the contractor. AOstrctures is not responsible for waterproofing.

● All hardware shall be installed per manufacturer specifications and within specified design limitations. AOstructures, Inc. assumes no responsibility for incorrectly installed hardware or hardware installed outside of the manfacturer specifications.

● Unless otherwise noted, construction material shall be evenly distributed if placed on framed floors or roofs. Loads shall not exceed the allowable loading for the supporting members and their connections.

● All members and hardware shall be either galvanized and/or stainless steel to resist corrosion due to the exterior environment they are intended to be installed in.

USER RELIANCE

● AOstructures was engaged by Lunar Energy (Client) to perform this assessment. This report and the information therein, are for the exclusive use of the Client. This report has no other purpose and shall not be relied upon, or used, by any other person or entity without the written consent of AOStructures. Third parties that obtain this report, or the information within shall have no rights of recourse or recovery against AOstructures, it’s officers or employees.


LG370N1K-A6

370W

The LG NeON® 2 is LG’s best selling solar module and one of the most powerful and versatile modules on the market today. The cells are designed to appear all-black at a distance, and the performance warranty guarantees 90.6% of labeled power output at 25 years.

C UL US

Features

Enhanced Performance Warranty

25-Year Limited Product Warranty

LG NeON® 2 Black has an enhanced performance warranty. After 25 years, LG NeON® 2 Black is guaranteed at least

The NeON® 2 Black is covered by a 25-year 90.6% of initial performance. limited product warranty. In addition, up to $450 of labor costs will be covered in the rare case that a module needs to be repaired or replaced.

Solid Performance on Hot Days LG NeON® 2 Black performs well on hot days due to its low temperature coefficient.

Roof Aesthetics

LG NeON® 2 Black has been designed with aesthetics in mind using thinner wires that appear all black at a distance.

When you go solar, ask for the brand you can trust: LG Solar

About LG Electronics USA, Inc.

LG Electronics is a global leader in electronic products in the clean energy markets by offering solar PV panels and energy storage systems. The company first embarked on a solar energy source research program in 1985, supported by LG Group’s vast experience in the semi-conductor, LCD, chemistry and materials industries. In 2010, LG Solar successfully released its first MonoX® series to the market, which is now available in 32 countries. The NeON® (previous MonoX® NeON), NeON®2, NeON®2 BiFacial won the “Intersolar AWARD” in 2013, 2015 and 2016, which demonstrates LG’s leadership and innovation in the solar industry.

Condential & Proprietary Condential and Proprietary

LG370N1K-A6

LG NeON®2 Black

Certifications and Warranty

General Data
Cell Properties (Material/Type) Monocrystalline/N-type
Cell Maker LG
Cell Configuration 60 Cells (6 x 10)
Number of Bushes 12EA
Module Dimensions (L × W × H) 1.740mm x 1.042mm x 40 mm
Weight 18.6kg
Glass (Material) Tempered Glass with AR coating
Backsheet (Color) Black
Frame (Material) Anoindized Aluminum
Junction Box (Protection Degree) IP 68 with 3 Bypass Dieses
Cables (Length) 1,100mm x 2EA
Connector (Type/Maker) MC 4MIC
Certifications and Warranty
Certifications* EC 61215-11-1-1/2016 EC 61730-12-2/2016
L.U.61730-1-2017 L.U.61730-2-2017
Certifications* ISO 9001 ISO 14001 ISO 50001
Certifications* GHSA 18001
Certifications* Salt Mist Corrosion Test IEC 61701-2012 Severity 6
Ammonia Corrosion Test EC 62716-2013
Module Fire Performance Type 2 (L.U.61730)
Fire Rating Class 3 (L.U.790, ULCORD C.1703)
Solar Module Product Warranty 25 Year Limited
Solar Module Output Warranty Linear Warranty*
Improved 1 year 98.5%, from 2-24th year -0.33%/year down, 90.6%/year 25

Temperature Characteristics

NMOT* [°C] 42 ± 3
Pmax [N/°C] -0.35
Voc [N/°C] -0.26
Isc [N/°C] 0.03

*NMOT (Nominal Module Operating Temperature): Irradiance 800 W/m Wind speed 1 m/s, Spectrum AM 1.5

Electrical Properties (NMOT)

10-005025 1002.0 / 39.4 (Distan ce betw een Grounding & Mounting Holes)

Model LG370N1K-A6
Maximum Power (Pmax) [W] 2.77
MPP Voltage (Vmpp) [V] 33.3
MPP Current (MPP) [A] 8.32
Open Circuit Voltage (Voc) [V] 39.4
Short Circuit Current (Isc) [A] 8.81

I-V Curves

Electrical Properties (STC)*

Number of Busbars

Model LG370N1K-A6
Maximum Power (Pmax) [W] 37.0
MPP Voltage (Vmp) [V] 35.5
MPP Current (Impp) [A] 10.43
Open Circuit Voltage (Voc +5%) [V] 41.9
Short Circuit Current (Icc +5%) [A] 10.96
Module Efficiency [%] 20.4
Power Tolerance [%] 0--3

Short Circuit Current (Isc 5%)

Operating Conditions
Operating Temperature [°C] -40→+85
Maximum System Voltage [V] 1,000 (UJ/EJ)
Maximum Series Fuse Rating [A] 20
Mechanical Test Load* (Front) [Pa/pst] 14001,
Mechanical Test Load* (Rear) [Pa/pst] 50001

*Based on IEC 61215-2 : 2016 (Test Load = Design Load x Safety Factor (1.5)) OHSAS 18001 Mechanical Test Loads 6,000Pa/5,400Pa based on IEC 61215:2005 Salt Mist Corrosion Test

*STC (Standard Test Condition): Irradiance 1000 W/m

Anodized Aluminium Measurement Tolerence of Pmax: 3% +

Number of Modules per Pallet [EA] 25
Number of Modules per 40 Container [EA] 650
Number of Modules per 5.7 Container [EA] 850
Packages Box Dimensions (L x W x H) [mm] 1,790 x 1,120 x 1,213
Packages Box Dimensions (n) [in] 70.5 x 44.1 x 47.8
Packages Box Gross Weight [kg] 500
Packages Box Gross Weight [lb] 1,102

70.5 x 44.1 x 47.8 Temperature Characteristics

Packaging Configuration Number of Modules per Pallet

Number of Modules per 53’ Container

Operating Conditions

Dimensions (mm/inch) 0.03 2, Ambient temperature 20°C,

LG Electronics USA, Inc.Solar Business Division2000 Millbrook DriveLincolnshire, IL 60069www.lg-solar.com

| Lunar System

Specifications
lunar
2026-03-03
Confidential & Proprietary
lunarenergy.com

Lunar Battery

Lunar Battery (AC ESS) is a fully-integrated solar battery system. It includes a hybrid inverter converts both solar and battery energy to power homes, and offers a range of energy storage capacity options. Lunar Battery can be further expanded with DC ESS units, bringing 24/7 reliable

System 10kWh 15kWh 20kWh 25kWh 30kWh
Model Number L2-ESS-10KWH L2-ESS-19KWH L2-ESS-20KWH L2-ESS-20KWH* L2-ESS-20KWH*
DC Expansion (1)LE-DC-UNIT (2)LE-DC-UNIT
Aggregate Energy 10kWh 15kWh 20kWh 25kWh 30kWh
Maximum Continuous AC Power 9.6kW full sun5kW no sun 9.6kW full sun7.5kW no sun 9.6kWFull sun and no sun 9.6kWFull sun and no sun 9.6kWFull sun and no sun
Max Load Start Capability$\textcircled{1}$ 80LRA 100LRA 134LRA 134LRA 134LRA
Solar Configuration DC-coupled and AC-coupled
Customer Interface Customer App, Installer App, Gridshare Fleet Portal, APIs, LEDs
Operating Modes Lunar AI,Solar Self-Consumption,Time-of-use,Backup
Advanced Software Features Outage Watch,VPP enabled,load control
Communication Wi-Fi(2.4GHz),4G/LTE(CATM1),Ethernet
Warranty 12.5Years38MWh AC throughput 12.5Years56MWh AC throughput 12.5Years75MWh AC throughput 12.5Year94MWh AC throughput 12.5 years113MWh AC throughput
Model Number 10-005025
Nominal Voltage 120/240 Vac Split Phase
Grid Frequency 60Hz
Maximum Battery DC Input Current 30A
Maximum PV DC Input Current 37.5A
Maximum PV DC Input Power 15kW
Operating Input Voltage 380-450Vdc
Peak Discharge Power, off-grid 15kW for 5s
Maximum Continuous Output Current 40A
Overcurrent Protection Device 50A Breaker
Output Voltage Range 210Vac-264Vac
Total Harmonic Distortion <5%
Power Factor 0.85 lagging to 0.85 leading
PV Rapid Shutdown Switch and System Disconnect Yes, lockable
CEC Solar to Home/Grid Efficiency 95.5%
Supported Islanding Devices Lunar Bridge,Lunar MSA Controller+ConnectDERMSA
Warranty 12.5 years

Confidential & Proprietary

Compliance
Certifications System: CAN(UL 9540, UL 9450A (indoor and outdoor), UL 1741 CRD PCS, UL 3141 [Issue 1]Inverter: UL 1741, UL 1741 SB, UL 1699B, CSA C22.2 No. 107.1
Grid Connection IEEE 1547.1-2020, IEEE 1547.1-2018, SunSpec IEEE 2030.5 / CSIP, CA Rule 21
Emissions FCC Part 15 Class B
Mechanical 10 kWh 15 kWh 20 kWh 25 kWh 30 kWh
Mechanical 34.8" x 24.4" x 13.5"(884 x 619 x 344mm) 45.5" x 24.4" x 13.5"(1156 x 619 x 344 mm) 56.1" x 24.4" x 13.5"(1425 x 619 x 344 mm) 66.8" x 24.4" x 13.5"(1696 x 619 x 344 mm) 77.4" x 24.4" x 13.5"(1967 x 619 x 344 mm)
Mechanical Inverter: 12" x 24.4" x 13.5" (305 x 619 x 344 mm)Top + Bottom Cover: 3" x 24.4" x 13.5" (75 x 619 x 344 mm)
Heaviest Individual Component 106 lb (48 kg)
Inverter Mass 42 lb (19 kg)
Total Assembly Mass (including brackets & covers) 305 lb (139 kg) 421 lb (191 kg) 540 lb (245 kg) 659 lb (299 kg) 778 lb (354 kg)
Mounting Floor or wall mounted
Environmental
Ingress Rating System: Type 3RInverter: Type 3R
Operating Temperature <4°F to 122°F (<20°C to 50°C)&nbsp;
Storage Conditions Absolute Limits: -4°F to 140°F (-20°C to 60°C) < 95% RH1 month: -4°F to 113°F (-20°C to 45°C) <60%RH2 months: 32°F to 95°F (0°C to 35°C) <60%RHUp to 24 months: 65°F to 82°F (18°C to 28°C) <60%RH
Altitude Up to 9843 ft (3000 m)
Operating Noise @ 1 m < 39.5 dB(A (Typical)< 57.5 dB(A (Maximum))

Confidential & Proprietary

DC Expansion Unit (DC ESS)

Lunar DC Expansion Unit is a UL9540-certified, 5kWh DC energy storage system unit (DC ESS) designed for easy expansion of battery energy clean energy to homes of all sizes. Key features include: • Seamless multi-day backup power with dynamic load control

System
Model Number LE-DC-UNIT
Rated Energy 5 kWh
Operating Voltage Range 190 Vdc - 225 Vdc
Maximum Continuous Power 2.5 kW (on grid and off-grid)
Peak Discharge Power, off-grid 3.75 kW (5s)
Cell Chemistry Lithium Iron Phosphate (LFP)
Warranty 12.5 years
Compliance
Certifications CAN/UL 9540, UL 9450A (indoor and outdoor), CAN/UL 1973, UN 38.3
Mechanical
Dimensions (L x W x D) 12" x 24.4" x 13.5"(305 mm x 619 mm x 344 mm)
Mass 106 lb (48 kg)
Ingress Rating Type 3R
Operating Temperature -4°F to 122°F(-20°C to 50°C)
Storage Conditions Absolute Limits:-4°F to 140°F(-20°C to 60°C)<95%RH1month:-4°F to 113°F(-20°C to 45°C)<60%RH2month:32°Fto95°F(0°Cto35°C)<60%RHUp to24 months:65°Fto82°F(18°Cto28°C)<60%RH
Altitude Up to9843ft(3000m)
State of Charge(SOC) <30%initial

Confidential & Proprietary

–4°F to 140°F (-20°C to 60°C) < 95% RH 1 month: capacity. Each DC expansipon unit features a individual wall bracket for secure, independent wall mounting. Units can be vertically installed to 3.75 kW (5s) Cell Chemistry PC 24-102993 MASTER FILE


Lunar Bridge

Lunar Bridge is a Microgrid Interconnection Device that automatically detects outages and seamlessly transitions between grid and island. It supports all home circuits with a service entrance rated load center.

System Mechanical
Model Number 90-06801A Dimension (L x W x D) 26.7" x 14.1" x 9"
Current Rating 200 A (677 x 358 x 228 mm)
Busbar Rating 200 A Mass 44 lbs (20 kg)
Off-Grid Switchover Time < 0.03s Mounting Wall or semi-flush mount
Overcurrent Protection Device Up to 200 A
Number of Panelboard Spaces 20 Spaces / 40 Circuits
AC Meter Integral +/- 0.2%External (Rogowski Coil); +/- 5%
Warranty 12.5 Years
Environmental
Operating Temperature -40°F to 140°F (-40°C to 60°C)
Ingress Rating NEMA 3R

Lunar Maximizer

The Lunar Maximizer is a DC-to-DC charge controller that connects to individual solar panel. It optimizes solar output via tracking the maximum power point, with real-time monitoring and rapid shutdown capability.

System
Model Number 10-00522E
Rated Input DC Power 650 W
Maximum Input Open Circuit Voltage (Voc) 75 Vdc²
MPPT Operating Voltage 20 Vdc - 60 Vdc
Maximum Input Short Circuit Current (Isc) 20 A
Maximum Output Current 16 A
PV String Length Typical site: 9 - 20 Maximizers Shaded PV: 9 - 24 Maximizers
Usable PV power per string 6.6 kW (higher nameplate rating allowed and will curtail)
Parallel Strings of Different Lengths or Orientations 3 Strings
Warranty 25 Years
Environmental
Operating Temperature -40°F to 185°F (-40°C to 85°C)
Ingress Rating IP66

Mechanical

Dimension (L x W x D) 6.9" x 6.7" x 1.7"(176 x 169 x 43 mm)
Mass 1.6 lbs (725 g)
Mounting Rack or panel mount
PV Connector Staubli MC4
Compliance
Certifications UL 1741, CSA C22.2.107
Emissions FCC Part 15 Class B
*A PV module is compatible if its nameplate specification, adjusted for site-specific cold temperature, is less than the Maximum input rated.

Confidential & Proprietary

lunarenergy.com

Lunar Maximizer Hub

The Lunar Maximizer Hub is a junction box that combines PV strings and ensure reliable, instantaneous coordination between Lunar Maximizers and the inverter.Rogowski Coils are flexible, air-core sensors that provide accurate, non-intrusive AC current measurements. These current transformers (CTs)

System
Part Number 90-004034
Operating Voltage 25-450Vdc
DC Inputs 3 DC PV strings(3+&3-wire terminals+1 ground terminal)
Maximum Current Per Terminal 50A
Terminal Wire Size Range 8AWG-20AWG(Red/Black)6AWG-16AWG(Ground)
Internal Communications Mesh Wi-Fi to Maximizers,PLC to Inverter
Warranty 25Years
Environmental
Operating Temperature -40°Fto185°F(-40°Cto85°C)
Ingress Rating NEMA 3R

Mechanical

Dimension(L x W x D) 11'x 12'x 4"(280x305x102mm)
Mass 2.3lbs(1050g)
Mounting Rail mounting or comp shingle flashing

Rogowski Coil CT

Compliance

Certifications UL 1741
Certifications CAN/CSA C22.2 No.107.1
Certifications CSA C22.2 No.290.

Rogowski Colis are flexible, air-core sensors that provide accurate, non-intrusive AC current measurements. These current transformers (CTs) seamlessly transmit telemetry to the Lunar System to enable partial home backup monitoring.

Specifications
Magnetlab Part Number RCT-180L-Coil
Rated Primary Current Up to 5000 Amp
Accuracy 0.5 Class per IEC 61869-2 Accuracy from 100 Amps to 15,000 Amps
Phase Displacement <0.5°
Power Supply 9-36 VDC required(Not included)
UL Max Voltage 600V on bare conductor BIL 10kV
RMS Voltage 10,000V for AC insulation Test(1min)
Rated Frequency 30-1,000Hz
Minimum Impendance 75kOhms
Environmental
UL Rated Ambient 55℃
Operating Temperature -15℃to65℃
Storage Temperature -45℃to80℃
UL Relative Humidity Rating 85%

Mechanical

Coil Diameter 6.0"
Insulated Leads Length:8ft,24AWG gray cable Rating:600V
Mass 0.40lbs(0.15kg)

Compliance

Certications

Certifications UL 2808, CAN.CSA C22.2 No.61010-1-12, IP64

ConnectDER

Lunar and ConnectDER make installations faster and simpler. Using ConnectDER’s IslandDER™ Meter Socket Adapter together with the Lunar Meter Socket Adapter Controller, installers can integrate the Lunar System quickly and efficiently.

Part Number V-1-A-64
Maximum Continuous Current 200A
Short Circuit Rating 22k AIC
Power 12V DC bus to/from Lunar MSAC, Max 5W power supply available to 3rd party system from grid side of MID (load side of meter)
Current Sensing ANSI 0.2 Accuracy Class CTs for Revenue Grade Sensing; Additional line and load side (of MID) Rogowski Coils at < 5% accuracy
Voltage Sensing Line and Load side (of MID) - 0.4% Accuracy at Ambient, 1% Across Temperature Range
MID Control Discrete open/close signals with 1ms input noise rejection, Actuation time < 15 ms
MID Rated Cycles 10,000
Warranty 12.5 years

Environmental

Dimension(L x W x D) 7.8"x6.7"x4.9"(198×170×124mm)With pluggable Connection Module
Mass 5.55 lbs./2.52 kgWith Connection Module and 6 ft analog cable
Mounting Blade interface with 4-jaw or 5 jaw meter socket
Electric Meter Compatibility Type 2S, and 12S
Meter Socket Compatibility Ringless,Ring-type,Lever,Horn Bypass
Manual MID Override Externally Accessible Switch,Protected by(Dry Contact)Interlocked Tool-Access Cover
Thermal Management Passive Cooling,Heat Sinks
Cable Connection Factory-Wired Pluggable Connection,Weathertight,Reversible at Top of MSA,Pre-attached connector to Lunar MSAC
Cable Length Just6"
Ingress Rating NEMA 3R
Enclosure Type UL 94 5VA flame rating
Ambient Operating Temperature -22 F to 149 F (-30°C to 65°C)

ETL File Number

Mechanical

Compliance

Certications

Lunar Meter Socket Adapter Controller (MSAC)

System
Model Number LE-MSAC-01
MSAC Connection Voltage 12 VDC
MSAC Connection Rating 0.35 A
Inverter Connection Voltage 13 VDC
Warranty 12.5 years
Environmental
Operating Temperature -40°F (-40°C) to 140°F (60°C)
Storage Temperature -40°F (-40°C) to 140°F (60°C)
Environment Indoor and outdoor
Ingress Rating Type 3R
Humidity 100%
Maximum Elevation 9,843 ft (3000m)

Mechanical

Dimension(L×W×D) 11.9in×7.02in×2.99in(303×178.4×76mm)
Mass 2.2lb(1kg)
Mounting Wall
Certifications UL 1741, UL CSA 61010-1, UL CSA 61010-02-30
Emissions FCC Part 15 Class B

Confidential & Proprietary

lunarenergy.com

The Lunar System, when paired with Eaton AbleEdge smart breakers, delivers a flexible and cost-effective way to extend backup power seamlessly transmit telemetry to the Lunar System to enable partial home backup monitoring.

Compatible Panels Lunar Bridge and any Eaton BR-style residential panels
Compatible PV inverters All CEC-listed solar inverters
Maximum Non-Lunar AC PV in backup 11, 5KWac combined
Maximum Distance from Lunar Bridge/MSA Controller Free air: 75 ft (23 m)Through 1 wall (wood/drywall): 30 ft (9 m)Through 1 wall (concrete/brick): 10 ft (3 m)
Commissioning Lunar Installer App
Warranty 10 years mechanical, 3 years electronics
Environmental
Ambient operating temperature -30 °C to +40 °C
Humidity 0% to 90%, noncondensing
Mechanical
Footprint 2-pole: Takes 2 spaces in a loadcenter

4 40/50/60A available today. Contact Lunar for 15/20/30A availability.

Compliance

Certications

System Layout

Certifications UL 943; CSA C22.2 No. 144.1-16, UL 486A-486B, CSA C22.2 No. 65, UL 489, CSA C22.2 No. 144.1, UL 1998, CSA C22.2 No. 0.8, UL 60730, FCC Part 15, ICES-003

SystemEnvironmental

Lunar System with Service Disconnect at Utility MeterLunar System with MSA and MSA Controller

Lunar System with MSA and MSA Controller

Confidential & Proprietary

Condential & Proprietary Condential and Proprietary

lunarenergy.com


Flush Mount Rail System

Save Time and Money

Low-cost rail-based PV module mounting system provides easy installation, simple wire management great strength and the best features on the market

Three Rail Heights

PV cables and wiring for module-level electronics ts

inside rails to avoid me consuming wire management.

Use Any Roof A�achments -

Our rails mount to Tamarack composion shingle

Best Wire Management - PV cables and wiring for module-level electronics fits inside rails to avoid time consuming wire management.

Use Any Roof Attachments - Our rails mount to Tamarack composition shingle flashings, S-5! metal roof clamps or any roof attachment that uses a 5/16-IN bolt.

One Wrench Size - Install with ease and minimal tools. 1/2-IN socket fits all fasteners.

UL 2703 Listed - All components meet UL standards and have Class A Fire Rating for Type1 and 2 modules.

PE Certified - Pre-stamped engineering letters available for all 50 states and DC.

Tamarack Solar Phone: 707-222-6240 Email: info@tamaracksolar.com

Rev#5e

Tamarack Flush Mount makes it easy to stock parts and quickly install a PV system

Three Rail Sizes

3.1-inch rail for heavy loads and longer spans, 2.3-IN for moderate snow loads and 1.6-IN rail for low-profile mounting and areas with low snow load.

L-Foot with Rail Mount Quickly and securely mount the rail from either side, to Tamarack composition shingle flashings, S-5! metal roof clamps or any roof attachment that uses a 5/16-IN bolt.

Comp Shingle Flashing Get superior waterproofing on composition shingle roofs. 10-IN x 8-IN black aluminum flashing fits over L-foot. Sealing washer is included. Use with 5/16-IN lag bolt.

Channel End Clamp This end clamp replaces the 50/50 clamp at the end of the row of modules for better aesthetics. For 2.3 and 1.6 rail only.

Push-In Bonding Rail Splice Quickly splice and bond rail sections with no tools or fasteners for 2.3 and 1.6 splices. Top Clamps and Rail Mounts can be co-located with splice.

One clamp can be used as a mid-clamp or an end-clamp on modules with 30mm to 40mm frame height. 5050+ Clamp is used for modules with frame height of 35mm to 46mm.

5050 Clamp

Push-On End Cap

Push-On End Cap Caps give the rail system a finished look while allowing drainage. Can be used with 50/50 Clamp or Channel End Clamp.

Wire Clip Clips can be pushed into top of rail to keep cables in place.

Ground Lug

Use one per module row to ground rail with bare 6 to 10 AWG copper wire.

Tamarack Solar

MLPE Mount

Use this adapter for mounting microinverters and optimizers on the rails under the modules.